Safe transformer operation depends on standardized inspection & maintenance. Inspection intervals should be adjusted according to site conditions: urban normal environment, Gobi‑desert dust, coastal salt‑fog or tropical high‑temperature zones. Below is practical checklist for oil‑immersed and dry‑type transformers.

1. Oil‑immersed Transformer Inspection Schedule

Monthly visual routine check

  1. Check oil‑level, oil colour and for oil leakage;
  2. Listen for abnormal operating noise;
  3. Inspect tank and radiator for corrosion;
  4. Check bushing surface for dirt, tracking or cracks;
  5. Verify ventilation and protective enclosures are intact.

Mandatory annual tests (at least once per year)

  1. Take oil sample for laboratory analysis (dielectric strength, moisture, acid value). Perform oil filtering or replacement when parameters fail limits.
  2. Measure winding DC resistance and insulation resistance.
  3. Bushing visual & insulation test.
  4. Inspect earthing connections, retighten loose bolts.

Overseas note: For dusty Central‑Asia, hot‑humid African sites, perform oil sampling every 6‑9 months (shortened from domestic yearly cycle).

2. Dry‑type Transformer Inspection Schedule

Basic cleaning & visual check (every 3 months; 1‑2 months for heavy‑dust sites)

  1. Blow dust off epoxy coil surface; inspect for cracks or peeling;
  2. Test cooling‑fan start‑stop function, check jamming or abnormal noise;
  3. Verify temperature‑controller reading accuracy;
  4. Check terminals for over‑heat discoloration and loose fasteners.

Comprehensive annual service

  1. Complete deep dust removal;
  2. Insulation‑resistance measurement;
  3. Retighten all connection bolts;
  4. Full function test for temperature controller and cooling‑fan assembly.

Overseas note: In heavy‑dust regions such as Central‑Asia and North‑Africa, shorten dust‑cleaning cycle to avoid overheating caused by blocked cooling paths.

3. Extra checks for harsh working conditions

  1. Dusty desert sites (Central‑Asia / North‑Africa): Focus on cooling‑path blockage and enclosure anti‑corrosion.
  2. Salt‑fog coastal sites: Pay attention to metal‑part corrosion and terminal rusting.
  3. Hot tropical zones (West Africa): Monitor operating temperature and confirm full cooling‑system performance.
  4. Perform additional special inspection after heavy rain or lightning storms.

4. Warning signs requiring immediate shutdown

‑ Oil‑immersed transformer: Dark degraded oil, heavy leakage, violent internal abnormal noise.

‑ Dry‑type transformer: Epoxy cracking, smoke emission, over‑temperature alarm.

‑ Frequent protective tripping events.

Do not keep transformers running under these fault conditions; cut off power and carry‑out troubleshooting.

Disclaimer: This checklist serves for reference only. All high‑voltage work must comply with local power‑safety regulations and be completed by certified professionals.

Conclusion: No transformer is lifetime maintenance‑free. Reasonable periodic inspection adapted to local conditions minimizes unexpected failures, extends service life and reduces total‑ownership‑cost.