Safe transformer operation depends on standardized inspection & maintenance. Inspection intervals should be adjusted according to site conditions: urban normal environment, Gobi‑desert dust, coastal salt‑fog or tropical high‑temperature zones. Below is practical checklist for oil‑immersed and dry‑type transformers.
1. Oil‑immersed Transformer Inspection Schedule

Monthly visual routine check
- Check oil‑level, oil colour and for oil leakage;
- Listen for abnormal operating noise;
- Inspect tank and radiator for corrosion;
- Check bushing surface for dirt, tracking or cracks;
- Verify ventilation and protective enclosures are intact.
Mandatory annual tests (at least once per year)
- Take oil sample for laboratory analysis (dielectric strength, moisture, acid value). Perform oil filtering or replacement when parameters fail limits.
- Measure winding DC resistance and insulation resistance.
- Bushing visual & insulation test.
- Inspect earthing connections, retighten loose bolts.
Overseas note: For dusty Central‑Asia, hot‑humid African sites, perform oil sampling every 6‑9 months (shortened from domestic yearly cycle).
2. Dry‑type Transformer Inspection Schedule

Basic cleaning & visual check (every 3 months; 1‑2 months for heavy‑dust sites)
- Blow dust off epoxy coil surface; inspect for cracks or peeling;
- Test cooling‑fan start‑stop function, check jamming or abnormal noise;
- Verify temperature‑controller reading accuracy;
- Check terminals for over‑heat discoloration and loose fasteners.
Comprehensive annual service
- Complete deep dust removal;
- Insulation‑resistance measurement;
- Retighten all connection bolts;
- Full function test for temperature controller and cooling‑fan assembly.
Overseas note: In heavy‑dust regions such as Central‑Asia and North‑Africa, shorten dust‑cleaning cycle to avoid overheating caused by blocked cooling paths.
3. Extra checks for harsh working conditions
- Dusty desert sites (Central‑Asia / North‑Africa): Focus on cooling‑path blockage and enclosure anti‑corrosion.
- Salt‑fog coastal sites: Pay attention to metal‑part corrosion and terminal rusting.
- Hot tropical zones (West Africa): Monitor operating temperature and confirm full cooling‑system performance.
- Perform additional special inspection after heavy rain or lightning storms.
4. Warning signs requiring immediate shutdown
‑ Oil‑immersed transformer: Dark degraded oil, heavy leakage, violent internal abnormal noise.
‑ Dry‑type transformer: Epoxy cracking, smoke emission, over‑temperature alarm.
‑ Frequent protective tripping events.
Do not keep transformers running under these fault conditions; cut off power and carry‑out troubleshooting.
Disclaimer: This checklist serves for reference only. All high‑voltage work must comply with local power‑safety regulations and be completed by certified professionals.
Conclusion: No transformer is lifetime maintenance‑free. Reasonable periodic inspection adapted to local conditions minimizes unexpected failures, extends service life and reduces total‑ownership‑cost.