1. Key Advantages of Oil-Immersed Transformers
- Superior Cooling Performance
Oil-immersed transformers use mineral oil for cooling, achieving 40%+ better heat dissipation than dry-types. 2024 tests show S13 models maintain 15-20℃ lower winding temperatures at full load. - Extended Service Life
Average lifespan reaches 25-30 years thanks to:
- Oil insulation slowing aging
- Sealed construction preventing oxidation
- Conservator tanks regulating pressure
- Cost Efficiency
| Type | Initial Cost | 10-Year TCO | Best For |
|————-|————-|————-|——————-|
| Oil S11 | ¥850/kVA | ¥1,200/kVA | Industrial plants |
| Dry SCB10 | ¥1,100/kVA | ¥1,500/kVA | Commercial buildings | - Maintenance Simplicity
Oil chromatography provides 3-6 month early warnings, while smart models now feature:
- Wireless oil/temperature monitoring
- Automatic fault alerts
- 5-year maintenance intervals
2. 4 Golden Selection Rules
- Capacity Calculation
Per GB/T 1094:
text
Required Capacity(kVA) = Max Load(kW) × 1.25(Safety Factor) / 0.9(Power Factor)
2024 Update: Solar/wind projects need +15% capacity buffer.
- Efficiency Choices
- S9 Series: Phasing out (banned by 2027)
- S11 Series: Best value (No-load loss ≤240W)
- S13 Series: Top performer (Saves ≥¥15,000/year)
- Environmental Adaptation
- High altitude: Derate 5% per 1000m
- Humid areas: IP55 protection
- Flammable zones: FR3 fire-resistant oil
- Supplier Evaluation
Must-have certifications:
□ ISO9001
□ State Grid qualified
□ Local service centers (≤24h response)
3. 4 Critical Maintenance Practices
- Oil Management
- Annual tests: Dielectric loss ≤0.05
- 5-year filtration: Particles ≤5μm
- Emergency: 50% water increase = Immediate shutdown
- Temperature Monitoring
- Normal: Top oil ≤85℃
- Warning: Hot spots ≥105℃
- New tech: Fiber-optic sensing (±1℃ accuracy)
- Electrical Testing

- Emergency Response
Troubleshooting guide:
- Abnormal oil level: Check seals before refilling
- Sudden oil spray: Cut power immediately
- Gas alarm: Sample analysis required